Conventional Intrinsically Safe Heat Detector
DCD-1E-IS is an Intrinsically Safe Conventional Rate of Rise Heat Detector with a 60° fixed temperature element designed for use in hazardous areas. The unit also features a remote indicator output
Intrinsically safe thermovelocimetric detector for conventional system. YBN-R/4-IS base required
- Description
Description
*Features*
Dimensions: Ø100 x 40 mm. ATEX II 1G EEx ia IIC T5 rating Twin fire LEDs allow 360° viewing
Electronics free mounting base
Remote indicator output
ATEX Classification to II 1G EEx ia IIC T5 Tamb=55 °C
Approved by LPCB and GL
Operating Voltage: 15 – 30 V dc
Quiescent Current (typ): 50 µA
Maximum Current in Alarm: 50 mA
Operating Temperature Range: -10 °C to + 55 °C
Ingress Protection Rating: IP63
Colour / Case Material: Ivory or White / ABS
Weight (g) / Diameter (mm) / Height (mm): 97 / 100 / 40
Compatible Base / Height (mm): YBN-R/4(IS) / 8